Input, current | Yes |
---|
Input, voltage | Yes |
---|
Input, resistor | No |
---|
Input, resistance thermometer | No |
---|
Input, thermocouple | No |
---|
Input signal, configurable | Yes |
---|
Output, current | No |
---|
Output, voltage | No |
---|
Output signal configurable | No |
---|
Analogue inputs configurable | Yes |
---|
Analogue outputs configurable | No |
---|
Type of electric connection | Screw-/spring clamp connection |
---|
Output range | -10…10V, 0…10V, 0…5V, 0…20 Ma |
---|
Module keying | Electronic, software configurable |
---|
Module error over full temperature range | 0.1 % |
---|
Module conversion method | R-Ladder DAC, monotonicity with no missing codes |
---|
Open circuit detection | Current output = Yes |
---|
Drive capability | Current output = 0...1000 Ω, Voltage output =>1000 Ω |
---|
Short circuit detection | Voltage output = Yes |
---|
Data format | IEEE 32-bit floating point |
---|
Wire category | 2 - on signal ports |
---|
Overvoltage protection | ±30V DC (voltage/current) |
---|
Settling time | <2 ms to 95% of final value with resistive loads |
---|
Total backplane power | Voltage mode = 6.3 W, Current mode with 250 Ω loads = 6.3 W, Current mode with 500 Ω loads = 7.6 W, Current mode with 750 Ω loads = 9.2 W, Current mode with 1000 Ω loads = 10.2 W |
---|
Module scan time | 1 ms minimum |
---|
Thermal dissipation | Voltage mode = 18.4 BTU/hr, Current mode with 250 Ω loads = 18.4 BTU/hr, Current mode with 500 Ω loads = 19.8 BTU/hr, Current mode with 750 Ω loads = 22.2 BTU/hr, Current mode with 1000 Ω loads = 22.9 BTU/hr |
---|
Current draw | 200 mA @ 5.1V, Voltage or current mode with 250 Ω loads = 220 mA @ 24V, Current mode with 500 Ω loads = 275 mA @ 24V, Current mode with 750 Ω loads = 340 mA @ 24V, Current mode with 1000 Ω loads = 385 mA @ 24V |
---|
Inputs | Eight isolated channels - any combination of voltage or current mode |
---|
Power dissipation | Voltage mode: 5.4 W (18.4 BTU/hr), Current mode with 250 Ω loads: 5.4 W (18.4 BTU/hr), Current mode with 500 Ω loads: 5.8 W (19.8 BTU/hr), Current mode with 750 Ω loads: 6.5 W (22.2 BTU/hr), Current mode with 1000 Ω loads: 6.7 W (22.9 BTU/hr) |
---|
Resolution | 16 bit, ±10.5V (0.32 mV/count), 0...10.5V (0.16 mV/count), 0...5.25V (0.08 mV/count), 0...21 mA (0.32 μA/count) |
---|
Wire size | 0.33...2.1 mm² (22...14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation maximum |
---|
Calibrated accuracy | 0.05% @ 25 °C (77 °F) |
---|
Suitable for safety functions | No |
---|
Output impedance | 46 Ω (Current output) |
---|