Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85362010 |
Data Sheet, Technical Information: | 9AKK107046A0423 |
Instructions and Manuals: | 2CSC400002D0208 |
Product Net Width: | 52.5 mm |
Product Net Depth / Length: | 69 mm |
Product Net Height: | 88 mm |
Product Net Weight: | 0.375 kg |
Standards: | IEC/EN 60898-1 IEC/EN 60947-2 |
Number of Poles: | 3 |
Tripping Characteristic: | C |
Rated Current (In): | 25 A |
Rated Operational Voltage: | acc. to IEC 60898-1 400 V AC acc. to IEC 60947-2 440 V AC |
Power Loss: | 9.6 W at Rated Operating Conditions per Pole 3.2 W |
Rated Insulation Voltage (Ui): | acc. to IEC/EN 60664-1 440 V |
Operational Voltage: | Maximum (Incl. Tolerance) 440 V AC Maximum 440 V AC Minimum 12 V AC Minimum 12 V DC |
Rated Frequency (f): | 50 Hz 60 Hz |
Rated Short-Circuit Capacity (Icn): | (400 V AC) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (230 V AC) 25 kA (440 V AC) 15 kA |
Rated Service Short-Circuit Breaking Capacity (Ics): | (230 V AC) 18.8 kA |
Energy Limiting Class: | 3 |
Overvoltage Category: | III |
Pollution Degree: | 3 |
Rated Impulse Withstand Voltage (Uimp): | 4 kV (6.2 kV @ sea level) (5.0 kV @ 2000 m) |
Dielectric Test Voltage: | 50 / 60 Hz, 1 min: 2 kV |
Housing Material: | Insulation Group II, RAL 7035 |
Actuator Type: | Insulation group II, black, sealable |
Contact Position Indication: | Red ON / Green OFF |
Degree of Protection: | IP20 |
Remarks: | IP40 in enclosure with cover |
Electrical Endurance: | 20000 AC cycle |
Mechanical Endurance (Nendu): | 20000 cycle |
Terminal Type: | Screw Terminals |
Screw Terminal Type: | Failsafe Bi-directional Cylinder-lift Terminal |
Connecting Capacity: | Busbar 10 / 10 mm² Flexible with Ferrule 0.75 ... 25 mm² Flexible 0.75 ... 25 mm² Rigid 0.75 ... 35 mm² Stranded 0.75 ... 35 mm² |
Tightening Torque: | 2.8 N·m |
Recommended Screw Driver: | Pozidriv 2 |
Mounting on DIN Rail: | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position: | Any |
Ambient Air Temperature: | Operation -25 ... +55 °C Storage -40 ... +70 °C |
Resistance to Shock acc. to IEC 60068-2-27: | 25g / 2 shocks / 13 ms |
Resistance to Vibrations acc. to IEC 60068-2-6: | 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In |
Environmental Conditions: | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
RoHS Status: | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
Maximum Operating Voltage UL/CSA: | 125 V DC 480Y/277 V AC |
Connecting Capacity UL/CSA: | Busbar 14-8 AWG Conductor 14-4 AWG |
Tightening Torque UL/CSA: | 18 in·lb |
Interrupting Rating acc. to UL1077: | (125 V DC) 10 kA (277 V AC) 6 kA (480Y / 277 V AC) 6 kA |
Declaration of Conformity - CE: | 2CDK403001D0605 |
Environmental Information: | 2CDK400030D0201 |
Instructions and Manuals: | 2CSC400002D0208 |
RoHS Information: | 2CDK400003K0203 |
Package Level 1 Units: | 1 piece |
Package Level 1 Width: | 92 mm |
Package Level 1 Depth / Length: | 58 mm |
Package Level 1 Height: | 80 mm |
Package Level 1 Gross Weight: | 0.4 kg |
Package Level 1 EAN: | 4016779606004 |
Package Level 2 Units: | 36 piece |
Package Level 2 Width: | 275 mm |
Package Level 2 Depth / Length: | 400 mm |
Package Level 2 Height: | 210 mm |
Package Level 2 Gross Weight: | 9.94 kg |
Package Level 2 EAN: | 4016779978231 |
Object Classification Code: | F |
ETIM 4: | EC000042 - Miniature circuit breaker (MCB) |
ETIM 5: | EC000042 - Miniature circuit breaker (MCB) |
ETIM 6: | EC000042 - Miniature circuit breaker (MCB) |
ETIM 7: | EC000042 - Miniature circuit breaker (MCB) |
eClass: | 7.0 27141901 |
UNSPSC: | 39121614 |