Range | Acti9 |
---|---|
Product name | Acti9 iDPN Vigi |
Product or component type | Residual current breaker with overcurrent protection (RCBO) |
Device short name | iDPN N Vigi |
Device application | Distribution |
Poles description | 1P + N |
Number of protected poles | 1 |
Neutral position | Left |
[In] rated current | 4 A |
Network type | AC |
Trip unit technology | Thermal-magnetic |
Curve code | B |
Earth-leakage sensitivity | 100 mA |
earth-leakage protection time delay | Instantaneous |
Earth-leakage protection class | Type A |
Breaking capacity | 6000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Complementary | Outgoer |
---|---|
Network frequency | 50 Hz |
[Ue] rated operational voltage | 220...240 V AC 50 Hz |
Magnetic tripping limit | 3...5 x In |
Residual current tripping technology | Voltage independent |
[Ics] rated service breaking capacity | 6000 A 100 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
Rated breaking and making capacity | Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
Limitation class | 3 conforming to EN/IEC 61009-2-1 |
[Ui] rated insulation voltage | 400 V AC 50 Hz |
[Uimp] rated impulse withstand voltage | 4 kV |
Contact position indicator | Yes |
control type | Toggle |
local signalling | ON, OFF, fault trip |
Mounting mode | Clip-on |
mounting support | DIN rail |
Comb busbar and distribution block compatibility | Top or bottom: YES |
Connection pitch | 9 mm between phase and neutral |
9 mm pitches | 4 |
height | 85 mm |
Width | 36 mm |
Depth | 73 mm |
Net weight | 125 g |
Colour | White |
Mechanical durability | 20000 cycles |
Electrical durability | 20000 cycles |
Locking options description | Padlocking device |
Connections - terminals | Single terminal top or bottom 1…16 mm² rigid Single terminal top or bottom 1…10 mm² flexible Single terminal top or bottom 1…10 mm² flexible with ferrule |
Wire stripping length | 15 mm for top or bottom connection |
Tightening torque | 2 N.m top or bottom |
earth-leakage protection | Integrated |
Standards | EN/IEC 61009-2-1 |
---|---|
Product certifications | VDE |
IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
Pollution degree | 3 |
Overvoltage category | III conforming to IEC 60364 |
Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1 |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
Ambient air temperature for operation | -25…60 °C |
Ambient air temperature for storage | -40…85 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 9.5 cm |
Package 1 Width | 3.6 cm |
Package 1 Length | 7.8 cm |
Package 1 Weight | 230 g |
Unit Type of Package 2 | BB1 |
Number of Units in Package 2 | 6 |
Package 2 Height | 10 cm |
Package 2 Width | 9 cm |
Package 2 Length | 25.5 cm |
Package 2 Weight | 1.43 kg |
Unit Type of Package 3 | S03 |
Number of Units in Package 3 | 54 |
Package 3 Height | 30 cm |
Package 3 Width | 30 cm |
Package 3 Length | 40 cm |
Package 3 Weight | 13.357 kg |
Warranty | 18 months |
---|