Range | Multi9 |
---|---|
Product name | Multi9 C60H-DC |
Product or component type | Miniature circuit-breaker |
Device short name | C60H-DC |
Device application | Distribution |
Poles description | 1P |
Number of protected poles | 1 |
[In] rated current | 2 A at 25 °C |
Network type | DC |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | 10 kA Icu at 220 V DC conforming to GB 14048.2 6 kA Icu at 250 V DC conforming to GB 14048.2 20 kA Icu at 110 V DC conforming to GB 14048.2 20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2 5 kA AIR at 12...250 V DC conforming to UL 1077 |
Utilisation category | Category A conforming to EN/IEC 60947-2 |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
[Ue] rated operational voltage | 12...250 V DC |
---|---|
Magnetic tripping limit | 8.5 x In +/- 20 % AC |
[Ics] rated service breaking capacity | 15 kA 75 % conforming to GB 14048.2 - 110 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 110 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 7.5 kA 75 % conforming to GB 14048.2 - 250 V DC 4.5 kA 75 % conforming to GB 14048.2 - 220 V DC |
Limitation class | 3 conforming to EN/IEC 60947-2 |
[Ui] rated insulation voltage | 500 V DC conforming to EN/IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
Contact position indicator | Yes |
control type | Toggle |
local signalling | ON/OFF indication |
Mounting mode | Clip-on |
mounting support | DIN rail |
Comb busbar and distribution block compatibility | Top or bottom: standard |
9 mm pitches | 2 |
height | 81 mm |
Width | 18 mm |
Depth | 73 mm |
Net weight | 0.128 kg |
Colour | Grey |
Mechanical durability | 20000 cycles |
Electrical durability | 3000 cycles L/R = 2 ms |
Provision for padlocking | Padlockable |
Locking options description | In position O |
Connections - terminals | Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1…10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1…10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1…10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded |
Wire stripping length | 14 mm for top or bottom connection |
Tightening torque | 2.5 N.m top or bottom |
earth-leakage protection | Without |
Standards | UL 1077 GB 14048.2 EN/IEC 60947-2 |
---|---|
Product certifications | UR CCC IEC |
IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
Pollution degree | 3 conforming to EN/IEC 60947-2 |
Overvoltage category | IV |
Tropicalisation | 2 conforming to IEC 60068-2 2 conforming to GB 14048.2 |
Relative humidity | 95 % at 55 °C |
Operating altitude | 2000 m |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…85 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 1.8 cm |
Package 1 Width | 7.1 cm |
Package 1 Length | 8.5 cm |
Package 1 Weight | 118 g |
Warranty | 18 months |
---|