Schneider Electric,LC1E0610M6,EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 6A - 220 V AC coil

(0 reviews)

Sold by:
Inhouse product

Price:
AED25.20 /pc

Quantity:
(4 available)

Total Price:
Share:
Main
RangeEasy TeSys
Range of producEasy TeSys Control
Product or component typeContactor
Device short nameLC1E
contactor applicationResistive load
Motor control
utilisation categoryAC-3
AC-1
Poles description3P
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current6 A (at <55 °C) at <= 440 V AC AC-3 for power circuit
20 A (at <55 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage220 V AC 60 Hz
Complementary
Motor power kW1.1 kW at 220...230 V AC 50/60 Hz
2.2 kW at 380...400 V
2.2 kW at 415 V
2.2 kW at 440 V
3 kW at 500 V
3 kW at 660...690 V
Pole contact composition3 NO
[Ith] conventional free air thermal current16 A (at 60 °C) for power circuit
Irms rated making capacity60 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity48 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current80 A 40 °C - 10 s for power circuit
45 A 40 °C - 60 s for power circuit
20 A 40 °C - 600 s for power circuit
Associated fuse rating10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
12 A gG at <= 690 V coordination type 1 for power circuit
Average impedance2.5 mOhm - Ith 20 A 50 Hz for power circuit
Power dissipation per pole0.09 W AC-3
1 W AC-1
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV coil not connected to the power circuit conforming to IEC 60947
Mechanical durability10000000 cycles
Electrical durability1400000 cycles AC-3
150000 cycles AC-1
Control circuit typeAC at 60 Hz
Control circuit voltage limits0.85...1.1 Uc (55 °C):operational 60 Hz
0.3...0.6 Uc (55 °C):drop-out 60 Hz
Inrush power in VA95 VA 50 Hz cos phi 0.75 (at 20 °C)
95 VA 60 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA8.3 VA 50 Hz cos phi 0.3 (at 20 °C)
8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
Heat dissipation2…3 W for control circuit
Operating time12...22 ms on closing
4...19 ms on opening
Maximum operating rate1800 cyc/h 60 °C
Connections - terminalsPower circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Tightening torquePower circuit: 1.2 N.m
Control circuit: 1.2 N.m
Auxiliary contact composition1 NO
Minimum switching voltage17 V for control circuit
Minimum switching current5 mA for control circuit
Insulation resistance> 10 MOhm for control circuit
Non-overlap time1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
mounting supportDIN rail
Plate
Environment
StandardsIEC 60947-4-1
IEC 60947-5-1
IEC 60947-1
product certificationsCE
EAC
IP degree of protectionIP2X conforming to IEC 60529
Protective treatmentTH (pollution degree 3) conforming to IEC 60068-2-30
Permissible ambient air temperature around the device-20…70 °C at Uc
-60…80 °C storage
-5…55 °C operation
Operating altitude3000 m without derating
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz)
Vibrations contactor closed (3 Gn, 5...300 Hz)
Shocks contactor open (7 Gn for 11 ms)
Shocks contactor closed (10 Gn for 11 ms)
height74 mm
Width45 mm
Depth80 mm
Net weight0.3 kg
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height8.31 cm
Package 1 Width7.4 cm
Package 1 Length4.82 cm
Package 1 Weight340 g
Unit Type of Package 2S02
Number of Units in Package 236
Package 2 Height15 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight12.648 kg
Contractual warranty
Warranty18 months
There have been no reviews for this product yet.

Product Queries (0)

Login or Registerto submit your questions to seller

Other Questions

No none asked to seller yet

Whatsapp